Similar presentations:
SIC Installation - Level 3 Service Technician – Installation
1.
2.
Top secretSecret
Internal use only
Public
Small Inverter Chiller
Service Product Training
Level 3 Service Technician – Installation
3.
2. SIC InstallationA. SIC Units
B. SIC Location
C. Lift SIC
D. Installation Foundation
E. Groupwork
F. Groupwork
4.
Build-UpHow to lift a Daikin Water Cooled Chiller on top of Mont Blanc in France?
5
SIC Installation - Internal use only
5.
2. SIC Installation6
SIC Installation - Internal use only
6.
2.A. SIC Units7
SIC Installation - Internal use only
7.
2.A. SIC UnitsEW*T-CZ**A2
EW*T-CZ**A1
EW*T-CZ**A1
40-90
32-40
16-25
Modules
2
1
1
Fans
3-4
2
1
Sizes
Note: Size 40 can be 1 module or 2
8
SIC Installation - Internal use only
8.
2.A. SIC UnitsR32 SIC Nomenclature
SIC: Small Inverter Chiller
Factory mounted options only available when ordering the unit
9
SIC Installation - Internal use only
9.
2.A. SIC UnitsSizes
Modules
10
SIC Installation - Internal use only
EW*T-CZ**A1
EW*T-CZ**A2
021, 032, 040
64
1
2
10.
2.A. SIC UnitsAlso available as a split version
EWYT-CZI & EWYT-CZO
•Split version of the EWYT-CZ
•HP only
•Models from 21 to 64kW
•All inverter: Compressor, fan and pump
•Same connectivity as EWYT-CZ
•R32 leak detector included in the Indoor
•No factory options
21
11
SIC Installation - Internal use only
32
40
64
Outdoor
1x EWYT021CZO-A1
1x EWYT032CZO-A1 1x EWYT041CZO-A1 1x EWYT064CZO-A2
Indoor
Circuits
1x EWYT021CZI-A1
1
1x EWYT032CZI-A1
1
1x EWYT041CZI-A1 1x EWYT064CZI-A2
1
2
11.
2.A. SIC UnitsEWYE-CZ**A2
EWYE-CZ**A1
EWYE-CZ**A1
30-70
30-35
20-25
Modules
2
1
1
Fans
3-4
2
1
Sizes
12
SIC Installation - Internal use only
12.
2.A. SIC UnitsR454C SIC Nomenclature
SIC: Small Inverter Chiller
Factory mounted options only available when ordering the unit
13
SIC Installation - Internal use only
13.
2.A. SIC UnitsUnit Works with F-gases
•F-gas Certificate
•Lightly Flammable gas
•Gas under pressure
•No smoking
•Wear gloves
•Wear eye protection
R32
R454C
R410A
Category
HFC
HFO
HFC
Formula
CH2F2
CH2
CH2F2 /
CHF2CF3
Composition
(Mixture Ratio
wt%)
-
R32/R1234yf
(21.5/78.5%)
R32/R125
(50/50 wt%)
Boiling
temperature
-51.7°C
-45.6°C
-51.5°C
ODP*1
0
0
0
GWP*2
675
148
2100
Slight
flammability
(A2L)
Slight
flammability
(A2L)
No
flammability
(A1)
No
No
No
Flammability
Toxicity
*1: Relative ODP values based on R12=1
*2: Information from IPCC 4th Assessment Report
14
SIC Installation - Internal use only
ESIE15-05 in
Daikin Portal
14.
2.A. SIC UnitsPaper documentation inside
Unit labels included:
•Model name plate
•Inlet & Outlet
Outlet
Inlet
15
SIC Installation - Internal use only
15.
2.A. SIC UnitsUnit includes following labels too:
•Lift instructions
•Fire risk
•Lift point
Safety gear:
•Helmet
•Glasses
•Gloves
•Headphones
•Safety shoes
16
SIC Installation - Internal use only
16.
2.B. Outdoor Location17
SIC Installation - Internal use only
17.
2.B. Outdoor LocationSelect a place where …
… the outdoor unit does not disturb neighbors.
… local legislation allows the unit to be installed
there.
18
SIC Installation - Internal use only
18.
2.B. Outdoor LocationSelect a place where …
… there are no obstacles for air flow.
… it is easy to access for service.
19
SIC Installation - Internal use only
19.
2.B. Outdoor LocationSelect a place where …
… the installation base can withstand the
outdoor unit’s weight and vibration.
… air flow is not obstructed, causing the
discharge air to by-pass at intake.
20
SIC Installation - Internal use only
20.
2.B. Outdoor LocationSelect a place where …
… the outdoor unit is not exposed to the
exhaust of other systems, oil, mist, dirt ...
21
SIC Installation - Internal use only
… the outdoor unit is not close to electrical
disturbance of GSM Antennas, Antennas …
21.
2.B. Outdoor LocationR32 Outdoor Unit installed Outside
•Ensure that in case of a leak the R32 won’t flow
within the building, ventilation system, doors…
•If R32 leak flows inside: apply same rules as if it was
installed inside
Install in compliance
of EN 378-3:2016
and local laws
R32 Outdoor Unit installed Inside
•Make a risk analysis
•Restricted access and dedicated room only
•Set up an alarm to the unit
•Ensure a ventilation system for operation and another
for emergencies
•Install detectors
•Comply with EN 378-3:2016
22
SIC Installation - Internal use only
More details for inside
installation in IM
22.
2.B. Outdoor LocationSelect a place where …
A : Electrical panel side
B/D : Side view of battery
C : Front view of battery
: Intake
A/B/C/D ≥ 500 mm
23
SIC Installation - Internal use only
… there is sufficient space around the unit for
servicing and air circulation.
23.
2.B. Outdoor LocationBeware of the sea
Avoid winds from the sea-side by placing it behind a building or a wall…
a. Sea wind
b. Building
c. Outdoor unit
d. Windbreaker
… to prevent corrosion caused by high levels of salt in the air
24
SIC Installation - Internal use only
24.
2.B. Outdoor LocationSelect a place where …
… there is sufficient space around the unit for
servicing and air circulation.
A: Front side of SIC
Suction Side of SIC
NOTE: In case the calculated value of A and/or C is higher than 2000mm, consider 2000mm as minimum distance.
25
SIC Installation - Internal use only
25.
2.B. Outdoor LocationBeware of the snow
…so the outdoor unit is not directly exposed to
heavy snow fall from above. In case of lateral
snow make sure the coils won’t be affected
If necessary, install a snow cover (field
supplied) or add a pedestal.
Beware of not blocking the air flow, contact
your dealer if necessary
26
SIC Installation - Internal use only
26.
2.C. Split Indoor Location27
SIC Installation - Internal use only
27.
2.C. Split Indoor LocationThe refrigerant charge amount brings limitations for indoor unit installation due to
flammability and toxicity of R32
What is the applicable standard?
Toxicity
Indicated by the capital letter A or B
Indicated by digits 1,2,3
Generic Standard: EN378
Product Standard: IEC60335-2-40
R32 is classified as a Lower Toxicity Refrigerant
Toxicity Limit(R32) = 0,30 kg/m3
For reference Toxicity Limit(R410A) = 0,44 kg/m 3
28
Flammability
SIC Installation - Internal use only
R32 is classified as a Lower Flammable
Refrigerant
Flammability Class: A2L
Max burning velocity ≤ 10 cm/s
28.
2.C. Split Indoor LocationDetermine the location and size of the room.
Different formulas to be used to calculate maximum refrigerant:
Toxicity limit
Other Floors
Lowest Underground Floor
advertising